VFD Sizing Calculator

Size the drive on amps, not horsepower.

Enter the nameplate, or photograph it. We return the continuous current the drive needs, the duty class, any derating for your site, and the drives on our shelf that match.

  • Sized on amps, not HP

    Drives trip on current. We size on FLA × duty margin; horsepower is shown for reference only.

  • Derated for your site

    Ambient above 40 °C and altitude above 1,000 m reduce a drive’s rating. We apply both before matching.

  • Matched to stock

    Results link straight to new and IAC-certified refurbished drives on the shelf in Raleigh, NC.

Size your VFD from the motor nameplate

Photograph the nameplate or type the values. Nothing is sent to sales until you ask. The example is a 20 HP rooftop fan at 460 V.

Motor

From the nameplate. FLA is what the drive is sized on.

Supply voltage
Input phases
Power unit

Leave FLA blank and we estimate it from NEC Table 430.250. Single-phase input cuts a drive’s usable rating to about 60%.Leave FLA blank and we estimate it from NEC Table 430.250.

Load and duty

Sets the duty margin and the Normal / Heavy duty class.

Load type
Service factor
Starts
Motors on this driveMotors on drive

Site conditions

Drives are rated at 40 °C and 1,000 m. Anything hotter or higher derates the drive.Rated at 40 °C and 1,000 m. Hotter or higher derates the drive.

The interface filters the shortlist for communications compatibility only. It does not change the sizing.

Sized on continuous current: FLA × duty margin, derated for site. Service factor counts as 1.00 on a drive; power is display-only.

VFDs in stock that match this motor

Drives at or above 29.7 A continuous on the 460 V class, sorted by fit. Same-day shipping from Raleigh, NC on orders placed by 4:00 PM Eastern.

    How VFD sizing works: amps first, horsepower second

    A drive protects itself on current. Two motors with the same horsepower can draw very different amps, so the nameplate FLA decides the size.

    • Start from FLA, not HP. Use the nameplate or NEC Table 430.250.
    • Add the duty margin for the load, then derate for heat, altitude and carrier frequency.
    • Treat service factor as 1.0 on an inverter-fed motor; the drive limits the current.

    Drive amps = FLA × duty margin ÷ (temperature × altitude × carrier factors)

    Then pick the next standard rating up. Single-phase input leaves about 60% of a drive’s three-phase rating.

    Duty margins and derating

    Typical values · check the drive manual

    Condition AdjustmentAdjustment Duty classDuty
    Fan or pump · variable torqueFan or pump +10% margin+10% Normal
    Conveyor or compressor · constant torqueConveyor or compressor +15% margin+15% Heavy
    Crane or mill · high inertiaCrane or mill +25% margin+25% Heavy
    Frequent starts · over 10 per hourFrequent starts +5% margin+5% —
    Several motors on one driveSeveral motors +25% margin+25% —
    Ambient above 40 °CAmbient above 40 °C −1% per °C−1% / °C —
    Altitude above 1,000 mAltitude above 1,000 m −1% per 100 m−1% / 100 m —
    Carrier frequency raisedCarrier frequency raised −10 to −35%−10 to −35% —

    Normal duty or heavy duty?

    Most drives carry two ratings on the same frame. The load type decides which one applies, and the wrong choice is the most common sizing mistake.

    • Normal duty

      110% overload for 60 seconds. Centrifugal loads that start light and never shock-load the motor.

      • Fans and blowers
      • Centrifugal pumps
      • HVAC and cooling towers
    • Heavy duty

      150% overload for 60 seconds. Loads that start under full torque or see sudden overloads.

      • Conveyors and compressors
      • Mixers and positive-displacement pumps
      • Cranes, hoists and mills
    • Worked example · Albuquerque fan

      20 HP, 27 A FLA, 1,620 m and 45 °C in the enclosure.

      • 27 A × 1.10 = 29.7 A
      • ÷ (0.95 ambient × 0.94 altitude) = 33.4 A
      • Next rating up: 34 A · ACH580-01-034A-4

    VFD derating for temperature and altitude

    A drive’s rating holds at 40 °C and 1,000 m. Hotter or thinner air carries away less heat, so the same drive delivers less current. The calculator applies both before it matches a drive.

    • Ambient means the air at the drive’s own intake. A sealed enclosure in a 35 °C plant can run well above 40 °C inside.
    • Above 2,000 m, thin air insulates as well as cools worse, so check the drive’s voltage class too.
    • Raising the carrier frequency for a quieter motor costs another 10 to 35%. Size for the carrier you will run.

    Usable amps = rated amps × temperature factor × altitude factor

    Factors multiply, they do not add. At 45 °C and 1,620 m: 0.95 × 0.94 = 0.89, so a 34 A drive delivers about 30 A.

    Derating factors the calculator applies

    1% per °C above 40 °C · 1% per 100 m above 1,000 m

    Site condition FactorFactor What it meansNote
    Ambient up to 40 °C (104 °F)Up to 40 °C × 1.00× 1.00 Full rating
    Ambient 45 °C (113 °F)45 °C × 0.95× 0.95 Often one frame larger
    Ambient 50 °C (122 °F)50 °C × 0.90× 0.90 Upper limit for most NEMA 1 drives
    Ambient above 50 °CAbove 50 °C × 0.85 at 55 °C× 0.85 at 55 °C Use a high-ambient drive or cool the enclosure
    Altitude up to 1,000 m (3,300 ft)Up to 1,000 m × 1.00× 1.00 Full rating
    Altitude 1,500 m (4,900 ft)1,500 m × 0.95× 0.95 Denver, Albuquerque
    Altitude 2,000 m (6,600 ft)2,000 m × 0.90× 0.90 Check the voltage class too
    Altitude 3,000 m (9,800 ft)3,000 m × 0.80× 0.80 Many families need a special rating

    Combined derating below about 0.70 usually calls for a different enclosure or forced cooling, not just a bigger drive.

    Motor full-load amps chart (NEC Table 430.250)

    Full-load current for three-phase induction motors at the common supply voltages. Use it to check a nameplate reading or to size before the motor arrives. When you have the nameplate, the nameplate wins.

    • Find the horsepower row and read the column for your supply voltage.
    • Add the duty margin and the site derating, then take the next drive rating up.
    • Leave FLA blank in the calculator above and it uses this table for you.

    Three-phase AC induction motors · full-load amps

    NEC Table 430.250 · amps

    HPkW208 V230 V460 V575 V
    ½0.372.42.21.10.9
    ¾0.553.53.21.61.3
    10.754.64.22.11.7
    1½1.16.66.03.02.4
    21.57.56.83.42.7
    32.210.69.64.83.9
    53.716.715.27.66.1
    7½5.524.222119
    107.530.8281411
    151146.2422117
    201559.4542722
    2518.574.8683427
    302288804032
    40301141045241
    50371431306552
    60451691547762
    75552111929677
    1007527324812499
    12590343312156125
    150110396360180144
    200150528480240192
    250185—604302242
    300220—722361289
    350260—828414336
    400300—954477382
    450335—1,030515412
    500375—1,180590472

    Code values for sizing conductors and protection, for squirrel-cage and wound-rotor motors at usual speeds. NEC lists 208 V values up to 200 HP. kW values are approximate.

    VFD sizing questions, answered

    Call (877) 727-8757 and an engineer will check the nameplate and overload duty with you.

    Can I size a drive by horsepower alone?

    Not safely. Drives are rated in continuous amps. Two 20 HP motors can differ by several amps, and the wrong one trips on overcurrent or runs the drive at its limit.

    Why does a correctly sized drive still trip on start?

    Usually one of four things: the load needs the Heavy Duty rating but the drive was picked on Normal Duty; the drive’s ambient is higher than expected because it sits in a sealed enclosure; the carrier frequency was raised without derating; or the motor draws more amps than its horsepower suggests.

    Should I use measured amps or nameplate FLA?

    Measure if you can. The nameplate tells you what the motor can draw; a clamp meter on the heaviest normal cycle tells you what the process actually demands. If the reading is at or above nameplate, size on the reading.

    Does single-phase input change the size?

    Yes. A three-phase drive fed from a single-phase supply delivers only about 60% of its rated current, so the calculator multiplies the required amps by 1.70. Many families also need a line reactor. If the supply is permanently single-phase, a drive rated for single-phase input is the cleaner choice.

    Can one drive run several motors?

    Yes, sized for the sum of the motor FLAs plus about 25%. Each motor still needs its own overload relay, the motors share one speed, and the drive has to run in V/Hz mode rather than sensorless vector.

    Do I need a braking resistor?

    Only if the load has to stop faster than it coasts, or it overhauls the motor, as on a hoist lowering or a high-inertia fan. The resistor must not fall below the drive’s minimum ohms, and its wattage follows the braking duty cycle.

    Not sure about the duty?

    Send the nameplate and a line about the load. An IAC engineer confirms the overload class, the derating and the drive, then quotes it, free of charge.

    (877) 727-8757 · sales@iac.us.com

    What to send

    • A nameplate photo, or HP, voltage, FLA and service factor
    • What the motor drives and how often it starts
    • Where the drive will live: ambient, altitude, enclosure