SINAMICS S120 parts guide

SINAMICS S120 parts guide

6SL3120-1TE24-5AA3 vs 6SL3120-2TE21-8AA3: Single vs Double Motor Modules, Sizing and Replacement

One drives a single 45 A axis. The other drives two axes at 18 A each. Here’s how to tell them apart, size the right one, and swap a failed module without rebuilding your project.

Two order numbers, three differences

The segments in blue are where these two modules differ.

6SL3 120- 1 TE 24-5 AA3 6SL3 120- 2 TE 21-8 AA3 SINAMICSDrive family Motor ModuleBooksize format Axes1 = single, 2 = double Voltage class600 V DC link Current code45 A vs 2 × 18 A VersionMatch it on replacement

What these two modules are

The 6SL3120-1TE24-5AA3 and the 6SL3120-2TE21-8AA3 are both SINAMICS S120 Motor Modules in Booksize format. A Motor Module is the inverter stage of an S120 drive line-up: it takes DC from the shared DC link, fed by a Line Module, and turns it into variable-frequency AC for a servo or induction motor. It has no brains of its own. A Control Unit such as the CU320-2 runs the closed-loop control and talks to each Motor Module over DRIVE-CLiQ.

The difference is how many motors each one runs. The 6SL3120-1TE24-5AA3 is a Single Motor Module rated 45 A for one axis. The 6SL3120-2TE21-8AA3 is a Double Motor Module with two independent 18 A inverters in one housing, so it runs two axes.

6SL3120-1TE24-5AA3

Single Motor Module, 45 A, Booksize

Check stock

6SL3120-2TE21-8AA3

Double Motor Module, 2 × 18 A, Booksize

Check stock

How to read the order number

6SL3 marks a SINAMICS product. 120 means a Booksize Motor Module. The digit after the dash is the number of axes: 1 for a Single Motor Module, 2 for a Double. TE places the module in the 600 V DC link class used on 380–480 V lines. The next three digits encode rated current per axis: 24-5 works out to 45 A and 21-8 to 18 A. The suffix, AA3 here, identifies the design version. When you replace a module, match the full order number, or confirm the successor on Siemens Industry Online Support before you order.

Specs side by side

6SL3120-1TE24-5AA3 6SL3120-2TE21-8AA3
Module type Single Motor Module Double Motor Module
Axes 1 2, controlled independently
Rated output current 45 A 18 A per axis
Rated power 24 kW 9.7 kW per axis
Peak current 85 A 36 A per axis
DC link voltage 510–720 V DC 510–720 V DC
Format and cooling Booksize, internal air cooling Booksize, internal air cooling
Control interface DRIVE-CLiQ DRIVE-CLiQ

Values are from Siemens SINAMICS S120 Booksize documentation. Confirm current, power and overload ratings against the Siemens datasheet for your application.

Single or double: how to choose

Both modules sit on the same DC link and 24 V busbars, so you can mix them in one line-up. The choice comes down to current, panel space and how much downtime one failure can cost you.

Pick the Double Motor Module when

  • Each axis needs 18 A continuous or less. Feed axes, indexers, conveyors and small spindles often fall here.
  • Panel width is tight. One double module takes less space than two singles of the same rating.
  • You want fewer components, fewer DRIVE-CLiQ cables and a lower cost per axis.

Pick the Single Motor Module when

  • The axis needs more than 18 A. At 45 A, the 6SL3120-1TE24-5AA3 covers larger servos and main drives.
  • The axis is critical and you want it on its own hardware. When a double module fails, both of its axes stop.
  • You expect to change one axis later without touching its neighbour.

Rule of thumb: two axes at 18 A or less that work together, such as X and Y on one machine, are a natural fit for a double module. Anything bigger, or anything you can’t afford to lose alongside another axis, goes on a single.

Sizing checklist

Size a Motor Module by current, not kilowatts. Work through these before ordering:

  1. Continuous current. Take the motor’s rated or stall current from its datasheet. The module’s rated current must cover it with margin.
  2. Peak current and duty cycle. Servo axes accelerate hard. Check that your peak current and how long you hold it fit inside the module’s overload profile, not just its peak number.
  3. Derating. Rated current drops at higher pulse frequencies, above about 40 °C ambient and above about 1,000 m altitude. Apply the derating curves from the Siemens manual.
  4. Line Module capacity. Add up the DC link power of every Motor Module on the line-up, apply a realistic simultaneity factor, and confirm the Line Module can supply it.
  5. Control Unit capacity. Adding axes adds drive objects. Check that the Control Unit can handle the axis count and control mode at your cycle times.

For a double module, size each axis on its own. Two 18 A axes don’t combine into one 36 A axis.

Common faults on S120 Motor Modules

These power unit faults are the ones most often traced to a Motor Module. Before you blame the module, check the motor, motor cable and load: many of these start outside the drive.

Fault Meaning Check first
F30001 Power unit overcurrent Motor cable insulation, shorted motor winding, mechanical jam, controller tuning too aggressive
F30002 DC link overvoltage Regenerative energy during braking, Line Module or braking resistor capacity, deceleration ramps
F30003 DC link undervoltage Line supply dips, Line Module faults, loose DC link busbar bridges
F30004 Heat sink overtemperature Fan, blocked airflow, dust, cabinet ambient temperature
F30005 Power unit overload (I²t) Undersized module for the duty cycle, binding mechanics, brake not releasing
F30021 Ground fault Motor cable damage, moisture in the motor or connectors

Fault texts summarised from the SINAMICS S120/S150 List Manual. Use the manual for your firmware version for full causes and remedies.

If a fault follows the module when you swap motor connections to another axis, or comes back immediately with the motor disconnected, the module itself is the likely cause. On a double module, a fault on one axis only may still point to a hardware failure that takes out both axes, so plan the replacement for the whole unit.

Replacing a failed module

Like-for-like replacement

Swapping in the same order number is the fastest way back to running. The project, topology and parameters stay the same.

  1. Record and back up. Note the order number, firmware and hardware version from the rating plate. Back up the drive project in Startdrive or STARTER, or make sure the Control Unit’s memory card is current.
  2. Isolate and wait. Lock out the supply, then wait the DC link discharge time printed on the module’s warning label before touching anything. Measure to confirm the DC link is discharged.
  3. Note the connections. Photograph or label the motor power, brake, DRIVE-CLiQ ports and the DC link and 24 V busbar bridges.
  4. Swap the module. Fit the replacement in the same slot, refit the busbar bridges and reconnect everything to the same ports.
  5. Power up and let firmware match. If automatic firmware update is enabled, the Control Unit brings the new module to the firmware on its memory card. Let it finish, then power-cycle as prompted.
  6. Accept the new component. Depending on your topology comparison setting, the Control Unit may flag the new serial number. Accept the replacement as described in the S120 commissioning manual, then save to non-volatile memory.
  7. Test. Run each axis at low speed before production. If the axes use Safety Integrated functions, carry out the acceptance steps your safety documentation requires after a component change.

Replacing a double with two singles, or the reverse

This is not a drop-in swap. Changing between Single and Double Motor Modules changes the DRIVE-CLiQ topology, the number of components and the panel width. You will need to edit the project in Startdrive or STARTER, re-wire DRIVE-CLiQ, confirm busbar and fusing arrangements, and re-commission the affected axes. If your goal is just to get a machine running again, replace like for like and plan any redesign separately.

New, IAC Certified Refurbished or repair

New

Latest production version with full factory documentation. The right choice for new builds and when you need a known-current design version.

IAC Certified Refurbished

Tested before shipping and covered by IAC’s 2-year warranty. Often the fastest and most cost-effective way to replace a failed module with the same order number.

Repair

Keeps your original unit, but the machine stays down while the module is out. Works best when you already have a spare installed.

Many plants do both: install a replacement today to restart production, then repair the failed unit to keep as a shelf spare. Send us your order number and we’ll tell you what we have in stock, new or refurbished.

FAQ

Can a 6SL3120-2TE21-8AA3 replace a 6SL3120-1TE24-5AA3?

No. The double module tops out at 18 A per axis, well below the 45 A single, and swapping types changes your drive topology. Replace a failed module with the same order number.

Can I put both modules on the same DC link?

Yes. Single and Double Motor Modules in Booksize format share the same DC link and 24 V busbars and can sit in one line-up, as long as the Line Module and Control Unit are sized for the total.

If one axis on a double module fails, can I keep running the other?

Sometimes, by deactivating the faulted drive object, but both axes share one housing and power section. Treat a hardware fault on either axis as a reason to replace the whole module.

Do I need to re-commission after a like-for-like replacement?

Usually not. With the same order number on the same DRIVE-CLiQ port, the Control Unit keeps the existing parameters. You may need to accept the new component and save, and Safety Integrated axes may need acceptance steps.