Ajout réussi
Le produit « » a été ajouté à votre devis.
SKU: IC693MDL240-FS
Ce produit n'est pas disponible à la vente en ligne.
Utilisez la rubrique « Demander un devis » pour obtenir les tarifs
The GE Fanuc IC693MDL240 is a 120 Volt AC input module designed for use with the Series 90-30 Programmable Logic Controllers. This module features 16 reactive input points that share a common power input terminal, facilitating connectivity with a variety of input devices, including limit switches, pushbuttons, and electronic proximity switches. When current is detected at an input point, the corresponding input status table (%I) displays a logic 1. It is essential to provide AC power to operate this module, as it is not compatible with direct current. The IC693MDL240 includes dual horizontal rows of eight green LEDs to indicate the ON/OFF status of each input. The top row (A1) refers to points 1 through 8, while the bottom row (B1) corresponds to points 9 through 16. Additionally, the module features a hinged door with an insert that allows users to document circuit wiring on the inner surface and circuit identification on the outer surface. The red color-coding along the left edge signifies its high-voltage classification. Compatible with both 5-slot and 10-slot baseplates of the Series 90-30 PLC system, the IC693MDL240 ensures seamless integration into existing control architectures. The module operates within a frequency range of 50/60 Hz, draws an input current of 12 milliamps at the rated voltage, and has a 1500-volt RMS isolation between the field and logic sides. Please note that the module consumes 90 milliamps from the 5-volt backplane bus.
The GE Fanuc IC693MDL240 is a 120 Volt AC input module designed for use with the Series 90-30 Programmable Logic Controllers. This module features 16 reactive input points that share a common power input terminal, facilitating connectivity with a variety of input devices, including limit switches, pushbuttons, and electronic proximity switches. When current is detected at an input point, the corresponding input status table (%I) displays a logic 1. It is essential to provide AC power to operate this module, as it is not compatible with direct current. The IC693MDL240 includes dual horizontal rows of eight green LEDs to indicate the ON/OFF status of each input. The top row (A1) refers to points 1 through 8, while the bottom row (B1) corresponds to points 9 through 16. Additionally, the module features a hinged door with an insert that allows users to document circuit wiring on the inner surface and circuit identification on the outer surface. The red color-coding along the left edge signifies its high-voltage classification. Compatible with both 5-slot and 10-slot baseplates of the Series 90-30 PLC system, the IC693MDL240 ensures seamless integration into existing control architectures. The module operates within a frequency range of 50/60 Hz, draws an input current of 12 milliamps at the rated voltage, and has a 1500-volt RMS isolation between the field and logic sides. Please note that the module consumes 90 milliamps from the 5-volt backplane bus.
The IC693MDL240E is a 16-point, 120 Volt AC input module designed for the Series 90-30 PLC system. It is widely used in industrial automation to read signals from pushbuttons, limit switches, and proximity sensors.
Note: This module provides 16 input points with one common power input terminal. It is designed to operate with a wide range of input devices.
16 Points
Single Common Group
120 VAC
Range: 0 - 132 VAC
30 ms
Typical On/Off Filter
The module features a block of 16 LEDs at the top. These LEDs indicate the ON/OFF status of each input point (A1 through B8) corresponding to the field wiring.
* The module state is undefined in the amber "Uncertain" zone.
| Parameter | Specification |
|---|---|
| Rated Voltage | 120 VAC (47 to 63 Hz) |
| Input Voltage Range | 0 to 132 VAC (RMS) |
| Input Current | 12 mA (Typical) at rated voltage |
| Isolation | 1500 Vrms (Field to Backplane) |
| Power Consumption | 90 mA (from +5V bus) |
Standard 20-pin terminal block configuration. Ensure Common (Pin 18) is connected to Neutral.
Ask questions about GE FANUC IC693MDL240
Posez des questions sur
Questions suggérées