A servo amplifier fault mid-shift doesn't wait for a manual to be found. Here's a cross-brand reference for Yaskawa Sigma-7, Mitsubishi MR-J, and Siemens SINAMICS S120 — with the first-action checks that actually resolve faults, and the misdiagnoses that waste the most time.
When a servo amplifier trips, the display gives you a code — not an answer. The temptation is to treat that code as the diagnosis itself: swap the drive, order the part, move on. But a large share of servo call-outs IAC's engineers hear about turn out to be wiring, encoder, mechanical binding, or parameter issues that a fault code merely points toward, not the drive amplifier failing outright.
This reference covers the three servo platforms IAC's customers ask about most: Yaskawa Sigma-7, Mitsubishi MR-J (J4/J5), and Siemens SINAMICS S120. For each, we've broken out the fault codes that come up most often on a shop floor, along with the first-action check before assuming the amplifier itself needs to be replaced.
This is a companion piece to IAC's PLC Fault Codes Decoded ↗ guide — together they cover the two systems most likely to trip a line to a stop with nothing more than a blinking code on a display.
Before reading any fault code table, it helps to know how each manufacturer structures its codes — because the format itself tells you something about severity and scope.
Alarms use "A." prefix (e.g., A.020); warnings that don't trip the drive use "A.9##". A separate "CN###" range covers communication-specific faults on network-connected amplifiers.
Alarms display as "AL." followed by a two or three-digit code. A decimal sub-code (e.g., AL. 32.1) often narrows the fault to a specific sub-cause within the main alarm number.
Five-digit codes prefixed "F" (fault — drive disables) or "A" (alarm — drive continues running). The digit ranges are grouped by subsystem: power section, communication, encoder, and motion control.
Knowing the prefix convention alone tells you whether you're looking at something that stopped the axis (a true fault) or something flagging a condition worth investigating before it becomes one (an alarm/warning). Don't reach for a replacement part until you've confirmed which category you're in.
The Sigma-7 series (SGD7S amplifiers) is one of the most widely deployed servo platforms in North American machine building. Most field calls trace back to a handful of recurring codes:
| Code | Description | First-Action Check |
|---|---|---|
| A.020 | Parameter checksum error | Confirm whether power was lost during a parameter write; restore from a saved parameter backup before assuming the amplifier's memory has failed |
| A.040 | Parameter setting error | Check for an out-of-range value entered during commissioning or a recent SigmaWin+ edit — this is a software condition, not a hardware fault |
| A.051 | Motor combination error | Verify the motor connected matches the amplifier's configured motor code — common after a motor swap where the amplifier wasn't re-commissioned |
| A.710 / A.720 | Overload — instantaneous / continuous | Check for mechanical binding, an undersized amplifier for the load, or an incorrect acceleration profile before assuming a drive fault |
| A.7A1 | Internal fan stopped | Inspect the fan physically — this is a genuine hardware fault and typically does require a replacement or repair |
| A.810 / A.820 | Encoder backup alarm / battery alarm | Replace the absolute encoder backup battery first; this is the single most common false "amplifier failure" call for Sigma-7 systems |
| A.b31 | Current detection error | Check motor cable and connector integrity for damage or moisture before replacing the amplifier — a cable fault often mimics this alarm |
| CN460 / CN808 | MECHATROLINK communication error / timeout | Verify network cabling, termination, and station addressing before suspecting either the amplifier or the controller |
Note that Sigma-7 warning codes (the "A.9##" range) do not trip the drive and often clear on their own once the underlying condition — typically an overload margin or regeneration warning — resolves. Don't schedule a replacement based on a warning code alone.
Yaskawa Sigma-7 amplifiers and encoder cables — in stock, tested, 2-year warranty
Shop Yaskawa Servo Parts →Mitsubishi's MR-J series is common in packaging, semiconductor, and precision assembly equipment. Its two-part code — the main alarm number plus a decimal sub-code — is often skipped over in the field, but the sub-code is usually what actually narrows the cause.
| Code | Description | First-Action Check |
|---|---|---|
| AL. 16 | Encoder initial communication error | Check encoder cable seating and shielding first — a loose connector at the encoder or amplifier end is the most frequent cause |
| AL. 20 | Encoder normal communication error | Look for intermittent cable damage or excessive cable flex at a moving axis before condemning the encoder itself |
| AL. 25 | Absolute position erase | Check the encoder backup battery voltage — this is a battery condition in the large majority of cases, not an encoder hardware failure |
| AL. 32 | Overcurrent | Inspect motor cable for a short or ground fault before replacing the amplifier; sub-code AL. 32.1 vs. 32.2 distinguishes hardware- vs. software-detected overcurrent |
| AL. 33 | Overvoltage | Check regenerative resistor connection and capacity for the application — common after an axis with high deceleration duty was added without resizing regen capacity |
| AL. 46 | Servo motor overheat | Verify motor thermal sensor wiring and actual motor case temperature — a wiring fault at the thermistor reads identically to a genuine overheat condition |
| AL. 50 / AL. 51 | Overload 1 / Overload 2 | Review the load duty cycle against the motor's rated torque curve before assuming an amplifier or motor defect |
| AL. 8A / AL. 8E | Network / communication error | Confirm SSCNET III/H or CC-Link IE cable integrity and correct station number configuration before suspecting the drive |
Mitsubishi MR-J4 & MR-J5 amplifiers, motors, and encoder cables — in stock, 2-year warranty
Shop Mitsubishi Servo Parts →The S120 drive system is common in multi-axis machine tool and packaging applications, often paired with an S7-1500 CPU running motion control. Its five-digit codes are grouped by subsystem, and the F/A prefix tells you immediately whether the axis has stopped or is still running under a flagged condition.
| Code | Description | First-Action Check |
|---|---|---|
| F07011 | Motor overtemperature | Check motor temperature sensor wiring and cooling before assuming a motor winding fault |
| F07321 | Encoder 1 — zero mark / signal fault | Inspect encoder cabling and connector seating; this is the SINAMICS equivalent of the "cable, not encoder" pattern seen across all three platforms |
| F30001 | Power unit overcurrent | Check motor cable insulation and for a phase-to-phase or phase-to-ground fault before replacing the power module |
| F30002 | Power unit overvoltage in DC link | Verify braking resistor / regenerative feedback module sizing and connection for the application's deceleration duty |
| F07803 | Motor overcurrent, "device overload" | Review load duty cycle and motion profile against the rated current of the configured motor module |
| F01018 | DRIVE-CLiQ topology fault | Check DRIVE-CLiQ cable connections and order — a single reseated connector resolves this more often than any component replacement |
| A07920 | Motor overload warning (alarm, not fault) | Monitor — the drive continues running. Investigate duty cycle if it recurs, but no immediate part is needed |
| A01590 | Communication warning, cyclic data exchange | Check PROFINET/DRIVE-CLiQ network loading and cabling; often resolves without a part swap once the network issue clears |
Siemens SINAMICS S120 power modules, control units, and DRIVE-CLiQ cables — in stock, 2-year warranty
Shop SINAMICS S120 Parts →Across all three platforms above, one pattern repeats more than any other: a fault code that names the drive or amplifier as the fault source actually traces back to the encoder cable — a loose connector, a pinched cable at a moving axis, or a failed connector shield letting in electrical noise. The amplifier reports what it sees (a lost or corrupted position signal), and what it sees looks identical whether the encoder itself failed or the signal simply never arrived cleanly.
The second most common misdiagnosis is treating an overload alarm as a defective amplifier when the real cause is a mechanical problem — a binding bearing, an undersized amplifier for a load that grew over time, or a motion profile with too aggressive an acceleration curve for the application. Swapping the amplifier in this case doesn't fix anything; the replacement unit will trip the same alarm on the same load.
None of this means the amplifier is never the problem — power section failures, blown IGBTs, and fan failures are real hardware faults. But running this checklist first, before a part is ordered, is the difference between a five-minute fix and an unnecessary replacement that doesn't resolve the actual fault.
Once a first-action check confirms the fault sits with the amplifier, motor, or encoder itself, IAC stocks certified replacement servo drives and components across Yaskawa Sigma-7, Mitsubishi MR-J4/MR-J5, and Siemens SINAMICS S120 — plus the motors, encoder cables, and backup batteries that resolve the majority of the field calls covered above.
Every servo drive IAC ships carries a 2-year in-service warranty — twice the industry standard for refurbished industrial components. Amplifiers are bench-tested under load before shipping, and encoder feedback is verified at the connector level, not just powered on and inspected visually.
In-stock servo parts ordered before 4:00 PM Eastern ship same day. For urgent needs, call (877) 727-8757 during business hours — quote turnaround is typically under five minutes. You can also submit a part number via the quote form ↗ or email sales@iac.us.com.
Yaskawa · Mitsubishi · Siemens servo drives, motors & encoder cables — all in stock, 2-year warranty
Browse Full Servo Drive Catalog →Yaskawa Sigma-7 · Mitsubishi MR-J · Siemens SINAMICS S120 — tested and in stock. Quotes in 5 minutes during business hours. Same-day shipping on in-stock units.