{"product_id":"honeywell-stryker-8-io-cvb4022as-vav1-u","title":"Honeywell Stryker, 8 IO - CVB4022AS-VAV1\/U","description":"\u003cp\u003eThe Honeywell Stryker 8 IO is a versatile Variable Air Volume (VAV) controller with a built-in actuator. It comes with 4 User Interfaces, 2 Analog Outputs and 2 Digital Outputs. Configurable to your needs, the controller utilizes the BACnet MS\/TP communication protocol and includes an RS-485 port.\u003c\/p\u003e\n\n\u003cp\u003eThis model features a built-in actuator (specific to the CVB4022AS-VAV1 model only) that mounts directly onto the VAV box damper shaft. The actuator provides torque of up to 44 lb-in (5 Nm), a 90-degree stroke, and a 90-second timing at 60 Hz. All wiring connections are made via removable terminal blocks, simplifying both installation and replacement procedures.\u003c\/p\u003e\n\n\u003cp\u003eThe Stryker 8 IO is rated for superior safety with UL Plenum, making both the controller housing and actuator highly rated. It functions as a stand-alone device but is also compatible with BACnet network communications for a fully integrated control system. It supports Sylk-enabled sensors through the Sylk™ bus and up to 30 controllers per BACnet MS\/TP segment.\u003c\/p\u003e\n\n\u003cp\u003eThis controller is field configurable for control, input, and output functions using the NIAGARA FRAMEWORK® software, and it includes built-in zone control functions. Users can control air volume through pressure-independent or dependent, and the device includes a Microbridge air flow sensor with dual integral restrictor design.\u003c\/p\u003e\n\n\u003cp\u003eOperating at a power supply of 24 VAC within a valid range of 20 to 30 VAC, the Stryker 8 IO functions efficiently in temperatures ranging from 0 to 50°C (32 to 122°F). Listed and approved widely, it comes with UL\/cUL (E87741) Listed under UL916 (Standard for Open Energy Management Equipment) with Plenum Rating CSA (LR95329-3). It meets FCC part 15, Subpart B, Class B (Radiated Emissions) requirements.\u003c\/p\u003e\n\n\u003cp\u003eThe Stryker 8 IO is intended for VAV applications and is mounted directly onto the damper shaft. Easy user access to air flow sensor inputs rounds up the extensive capabilities of this advanced Honeywell controller.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":46474908795116,"sku":"CVB4022AS-VAV1\/U","price":0.0,"currency_code":"CAD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0217\/1112\/6600\/files\/Honeywell_Group_Photo_-_Final_Compressed_ad50fbba-cc15-41fc-9f90-ab20cf3516d7.jpg?v=1763026104","url":"https:\/\/www.industrialautomationco.com\/en-ca\/products\/honeywell-stryker-8-io-cvb4022as-vav1-u","provider":"Industrial Automation Co.","version":"1.0","type":"link"}